GE D90 Plus Instruction Manual page 349

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
Multi-shot operation
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 277: Autoreclose scheme breaker close logic
Figure 278: Autoreclose scheme close breaker 1 or 2 logic
Figure 279: Autoreclose scheme termination
The
Maximum Number of Shots
reclose the shot counter is incremented.
If
Maximum Number of Shots
At reclosing, the fault is again detected by protection and reclose is initiated. The breaker is
tripped three-pole through the
operand. Because the shot counter has reached the maximum number of shots permitted,
the scheme is sent to the lockout state.
If
Maximum Number of Shots
At reclosing, the fault is again detected by protection and reclose is initiated. The breaker is
tripped three-pole through the
operand. After the second reclose the shot counter is set to 2. Upon reclosing, the fault is
again detected by protection, the breaker is tripped three-pole, and reclose is initiated
again. Because the shot counter has reached the maximum number of shots permitted,
the scheme is sent to the lockout state.
setting defines the number of reclose attempts. After each
is set to "1", the shot counter is set to 1 upon the first reclose.
operand that will set the
AR SHOT COUNT >0
is set to "2", the shot counter is set to 1 upon the first reclose.
operand that will set the
AR SHOT COUNT >0
CONTROL ELEMENTS
AR FORCE 3P
AR FORCE 3P
339

Advertisement

Table of Contents
loading

Table of Contents