IEC 61850 COMMUNICATIONS
Configurable GOOSE reception
114
VLAN ID
Range: 0 to 4096 in steps of 1
Default: 0
This setting allows the selection of a specific VLAN ID for each GOOSE sending device.
This value can be left at its default if the feature is not required.
ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
ConfRev
Range: 1 to 16383 in steps of 1
Default: 1
This value changes automatically as described in IEC 61850 part 7-2.
Minimum Time to Live
Range: 50 to 4000 ms in steps of 1
Default: 400 ms
This setting specifies the minimum time to live for the GOOSE transmission data set.
Retransmission Profile
Range: None, Aggressive, Standard, Relaxed
Default: Standard
Plus
The D90
supports four retransmission schemes: aggressive, standard, relaxed, and
none. In general, the "Aggressive" profile is selected for trip schemes, the "Standard"
profile for remedial action schemes, the "Relaxed" profile for analogue data sets, and
"None" for schemes that incorporate a separate confirmation scheme.
The following retransmission times are specified under these profiles.
"Aggressive": 4, 8, 16, 32, and 64 ms.
"Standard": 16, 32, 64, 128, and 256 ms (default).
"Relaxed": 100, 200, 400, 800, and 1000 ms.
"None": no retransmission.
These selections are available on a transmit dataset-by-dataset basis. For GSSE and
fixed GOOSE, the profile is fixed at "Aggressive" and there is no associated setting.
Dataset Item 1, Dataset Item 2, Dataset Item 3,..., Dataset Item 64
Range: all valid MMS data item references for transmitted data
Default: 0
These settings are used to select an MMS data item for each configurable GOOSE
dataset item.
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status
indication and its associated quality flags, the following dataset items can be selected:
"GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The D90
containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined
by the operand assigned to GGIO1 indication 1. Changes to this operand will result in the
transmission of GOOSE messages containing the defined dataset.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Reception > Rx Configurable GOOSE menu item to open the configurable GOOSE
reception configuration window.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
will then create a dataset