CHAPTER 6: COMMUNICATIONS
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
configuration is possible, but third-party substation configuration software may be used to
automate the process. The EnerVista UR
files and import IEC 61850 SCD files produced by a substation configurator.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Transmission > Tx Configurable GOOSE menu item to open the configurable GOOSE
transmission configuration window.
Figure 92: Configurable GOOSE transmission configuration settings
The following settings are available for each dataset for configurable GOOSE transmission.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disabled the configurable GOOSE transmission functionality.
ID
Range: up to 65 ASCII characters
Default: GOOSEOut_1
This setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as
part of each GOOSE message. This name string identifies the GOOSE message to the
receiving device.
Destination MAC
Range: standard MAC address format
Default: 00 00 00 00 00 00
This setting specifies the destination Ethernet MAC address for the configurable GOOSE
transmission. This address must be a multicast address and the least significant bit of
the first byte must be set.
If this setting is specified as "00 00 00 00 00 00" (the default value), then a multicast MAC
address is formed based on the MAC address of Ethernet ports 2 and 3. The MAC address
of Ethernet port 2 is the MAC address of Ethernet port 1 incremented by 1. Likewise, the
MAC address of Ethernet port 3 is the MAC address of Ethernet port 1 incremented by 2.
VLAN Priority
Range: 0 to 7 in steps of 1
Default: 4
This setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE
messages to have higher priority than other Ethernet data. This setting is required by IEC
61850.
IEC 61850 COMMUNICATIONS
Plus
Setup software can produce IEC 61850 ICD
113