Battery Monitor; Indications And Wiring - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 9: EQUIPMENT MANAGER

Battery monitor

Indications and wiring

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 428: Breaker arcing current logic
The battery monitor function monitors the health of the DC battery system. It provides an
analog indication of the current DC voltage derived from a contact input wired between
the positive and negative rails of the battery system. This signal is used to generate high
and low DC voltage alarms. This function also monitors and conditions the auxiliary alarm
contacts from the battery charger.
There is no battery inside the D90
The following indications and alarms are provided for the battery monitor function.
Battery monitor alarms and indications
BATTERY VOLTAGE..............................Displays the present value of the battery voltage.
HIGH DC VOLTAGE..............................Indicates the battery DC voltage is greater than the
LOW DC VOLTAGE...............................Indicates the battery DC voltage is less than the minimum
SUPPLY FAIL..............................................Indicates the AC supply to the battery charger has failed.
CHARGER FAIL.......................................Indicates the battery charger has failed.
BREAKER TRIP........................................Indicates a DC distribution breaker has operated.
Plus
.
maximum setting value.
setting value.
BATTERY MONITOR
497

Advertisement

Table of Contents
loading

Table of Contents