Flexstate Settings; Flexstate Actual Values - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 6: COMMUNICATIONS

FlexState settings

FlexState actual values

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
sixteen (16) states may be read out in a single Modbus register. The state bits can be
configured so that all of the states which are of interest to the user are available in a
minimum number of Modbus registers.
The state bits may be read out in the FlexStates register array beginning at Modbus
address 0900h. Sixteen states are packed into each register, with the lowest-numbered
state in the lowest-order bit. There are 16 registers in total to accommodate the 256 state
bits.
Select the Settings > Communications > Flex States menu item to open the FlexStates
configuration window.
Figure 114: Flex States configuration settings
The following settings are available.
Parameter 1 through Parameter 256
Range: any FlexLogic™ operand
Default: Off
These settings assign FlexLogic™ parameters to each of the 256 FlexStates. The
FlexState register array begins at Modbus address 0900h.
Select the Actual Values > Communications > FlexStates menu item to open the
FlexStates actual values window.
FLEXSTATES
139

Advertisement

Table of Contents
loading

Table of Contents