CHAPTER 6: COMMUNICATIONS
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 126: Interlocking busbar protection scheme via direct inputs and outputs
The following settings should be applied to implement this application. For IED 1, set the
inter-relay application for both channels as follows in the Settings > Communications >
Inter-Relay menu. If there are more than two IEDs in a ring configuration, then one device
(for example, IED 1) must have it's protocol encoding set as an internal clock and the
remaining devices have their protocol encoding set as external clock if no multiplexer is
used.
Figure 127: Inter-relay communications settings for IED 1
For IEDs 2 through 4, set the inter-relay application for both channels as follows in the
Settings > Communications > Inter-Relay menu.
Figure 128: Inter-relay communications settings for IEDs 2 through 4
Plus
For UR
-series IED 1:
DIRECT INPUTS AND OUTPUTS
151