CHAPTER 6: COMMUNICATIONS

IEC 60870-5-104 communications

IEC 60870-5-104 protocol settings

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DNP Binary Input Point 0, DNP Binary Input Point 1,..., DNP Binary Input Point 255
Range: any FlexLogic™ operand
Default: Off
These settings represent DNP binary input points and are configured by assigning an
appropriate FlexLogic™ operand. Up to 256 binary input points can be configured for
the DNP protocol.
DNP Analog Input Point 0, DNP Analog Input Point 2,..., DNP Analog Input Point 255
Range: any FlexAnalog™ parameter
Default: Off
These settings represent DNP analog input points and are configured by assigning an
appropriate FlexAnalog™ parameter. Up to 256 analog input points can be configured
for the DNP protocol.
The IEC 60870-5-104 server can support two clients simultaneously. It is capable of
reporting any indication or measurement and operating any output present in the device.
These point lists are shared with the DNP protocol.
Select the Settings > Communications > IEC 60870-5-104 > Protocol menu item to open
the IEC 60870-5-104 protocol configuration window.
Figure 87: IEC 60870-5-104 protocol configuration settings
The following settings are available for the IEC 60870-5-104 protocol.
IEC TCP Port Number
Range: 0 to 65535 in steps of 1
Default: 2404
This setting specifies the TCP port number to use for IEC 60870-5-104 communications.
IEC Client Address 1, IEC Client Address 2,..., IEC Client Address 5
Range: standard IP address format
Default: 0.0.0.0
These settings specify the IP addresses for five IEC 60870-5-104 clients.
IEC 60870-5-104 COMMUNICATIONS
107