PROTECTION INPUTS AND OUTPUTS
Protection virtual output actual values
384
Figure 323: Protection virtual output settings
The following settings are available for each protection virtual output. If not assigned, the
virtual output will be forced to off (logic 0).
ID
Range: up to 12 alphanumeric characters
Default: Virt Op 1
This setting specifies an identifier that may be assigned to each protection virtual
output.
Events
Range: Enabled, Disabled
Default: Disabled
If this setting is "Enabled", every change in the protection virtual output state will trigger
an event in the sequence of events recorder.
Select the Actual Values > Protection > Protection Inputs/Outputs > Virtual Outputs
menu item to open the protection virtual outputs actual values window.
Figure 324: Protection virtual output actual values
The following actual values are available for all configured protection virtual outputs.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION