DNP COMMUNICATIONS
NOTE:

DNP user point list

106
Points not configured as paired operate on a one-to-one basis.
DNP TCP Connection Timeout
Range: 10 to 300 seconds in steps of 1
Default: 120 seconds
This setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by
this setting, the connection will be aborted by the D90
to be re-used by a client.
Plus
Power to the D90
must be re-cycled after changing this setting for the changes to take
effect.
The binary and analog inputs points for the DNP protocol can configured to a maximum of
256 points. The value for each point is user-programmable and can be configured by
assigning FlexLogic™ operands for binary inputs or FlexAnalog™ parameters for analog
inputs.
The DNP point lists always begin with point 0 and end at the first "Off" value. Since DNP
point lists must be in one continuous block, any points assigned after the first "Off" point
are ignored. Changes to the DNP point lists will not take effect until the D90
Select the Settings > Communications > DNP > User Point List menu item to open the
DNP user point list configuration window.
Figure 86: DNP user point list configuration settings
The following settings are available for points 0 through 255.
Figure 85: Paired points list
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
. This frees up the connection
Plus
is restarted.