GE D90 Plus Instruction Manual page 380

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CONTROL ELEMENTS
Breaker flashover settings
370
Select the Settings > Protection > Control > Breaker Flashover menu item to open the
breaker flashover configuration window.
Figure 308: Breaker flashover configuration settings
The following settings are available for each breaker flashover element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disabled the breaker flashover protection element.
Side 1
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting specifies a signal source used to provide three-phase voltages and three-
phase currents from one side of the current breaker. The source selected as a setting
and must be configured with breaker phase voltages and currents, even if only three VTs
are available across the breaker.
Side 2
Range: None, LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Plus
Default: varies with UR
This setting specifies a signal source used to provide another set of three phase voltages
whenever six VTs are available across the breaker.
Status Closed A, Status Closed B, Status Closed C
Range: any FlexLogic™ operand or shared operand
Default: BKR1 CLOSED
These settings specify operands to indicate the open status of the breaker. A separate
operand can be selected to detect individual breaker pole status and provide flashover
detection. The recommended setting is 52a breaker contact or another operand
defining the breaker poles open status.
-series model; refer to the EnerVista UR
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION