Settings Ranges And Values - GE MLP1000 Manual

Microprocessor based distance protection
Table of Contents

Advertisement

1 to 7 in steps of 0.1
Positive sequence angle:
Homopolar sequence angle: 10° to 90° in 0.5° steps
Operating time setting:
Zone I:
Zone II:
Zone III: 120 ms to 10 s in 1 ms steps
Protection Schemes: Scaled distance
The scaled distance protection scheme is active even if one of the other two
protection schemes is selected.
RECLOSER SETTING RANGES (MLP2000 and MLP 3000)
Number of recloses: 0, 1, 2, 3 (setting 0 disables the recloser)
Reclosing time:
Closing time:
Reset time:
Delay time:
OSCILLOGRAPHIC REGISTER (MLP3000 and MLP4000)
Number of oscillograms:
Number of cycles per oscillo: 240
DIMENSIONS
1 four height standard 19" rack

3.3 SETTINGS RANGES AND VALUES

General settings:
001 IDENTIFICATION:
20 characters ASCII to identify each MLP unit. The identification can be
modified only through serial communications with the relay. It cannot be
modified from the keyboard
GEK-98846A
10° to 90° in 0.5° steps
0 to 500 ms in 1 ms steps
100 ms to 3 s in 1 ms steps
Zone I extension
Zone II acceleration (requires communications channel)
From 0.2 to 99s in 0.01s steps
From 0.1 to 99 s in 0.01 s steps
From 0.1 to 99 s in 0.01 s steps
From 0.1 to 99s in 0.01 s steps
7
11