Settings; Interlocking For Bus-Coupler Bay Abc_Bc - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
12.3.5.6
12.3.6
Technical manual
Name
Type
S1QC1_CL
BOOLEAN
S2QC2_OP
BOOLEAN
S2QC2_CL
BOOLEAN
S1DC_OP
BOOLEAN
S2DC_OP
BOOLEAN
VPS1_DC
BOOLEAN
VPS2_DC
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_BB
BOOLEAN
QBCL_EX1
BOOLEAN
QBCL_EX2
BOOLEAN
QBOP_EX1
BOOLEAN
QBOP_EX2
BOOLEAN
QBOP_EX3
BOOLEAN
Table 242:
A1A2_DC Output signals
Name
Type
QBOPREL
BOOLEAN
QBOPITL
BOOLEAN
QBCLREL
BOOLEAN
QBCLITL
BOOLEAN
DCOPTR
BOOLEAN
DCCLTR
BOOLEAN
VPDCTR
BOOLEAN

Settings

The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).

Interlocking for bus-coupler bay ABC_BC

Default
Description
0
QC1 on bus section 1 is in closed position
0
QC2 on bus section 2 is in open position
0
QC2 on bus section 2 is in closed position
0
All disconnectors on bus section 1 are in open
position
0
All disconnectors on bus section 2 are in open
position
0
Switch status of disconnectors on bus section 1 are
valid
0
Switch status of disconnectors on bus section 2 are
valid
0
No transmission error from bays containing
earthing switches QC1 or QC2
0
No transmission error from bays with
disconnectors connected to sections 1 and 2
0
External close condition for section disconnector
QB
0
External close condition for section disconnector
QB
0
External open condition for section disconnector
QB
0
External open condition for section disconnector
QB
0
External open condition for section disconnector
QB
Description
Opening of QB is allowed
Opening of QB is forbidden
Closing of QB is allowed
Closing of QB is forbidden
The bus section disconnector is in open position
The bus section disconnector is in closed position
Switch status of QB is valid (open or closed)
Section 12
Control