PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
Parameter
Write access with
operating mode
(MODE_BLK)
MANUFAC_ID
read only
MAX_NOTIFY
read only
MEMORY_
read only
SIZE
MIN_
read only
CYCLE_T
MODE_BLK
AUTO - OOS
NV_CYCLE_T
read only
Resource Block / base index 258
Description
Displays the manufacturer's ID number.
Display:
452B48 (hex) for Endress+Hauser
Displays the maximum number of event reports supported by the
device that can exist unconfirmed at the same time.
Display:
24
Displays the available configuration memory in Kbytes.
Note!
This parameter is not supported.
Displays the shortest block execution time which is supported by
PROline Prosonic Flow 93 FOUNDATION Fieldbus.
Display:
1
ms ( ≅ 50 ms)
1600
/
32
Displays the current (Actual) and desired (Target) operating mode
of the Resource Block, the permitted modes (Permitted) supported
by the Resource Block and the normal operating mode (Normal).
Display:
AUTO (automatic mode)
In this operating mode, the execution of the remaining blocks
(Transducer Blocks, AI, DO and PID function blocks) is enabled.
OOS, Out of Service
The block has the status "Out of Service". In this operating mode,
the execution of the remaining blocks (Transducer Blocks, AI, DO
and PID function blocks) is blocked. These blocks cannot be set to
AUTO mode.
Note!
The current operating status of the Resource Block is also shown
via the RS_STATE parameter, (see Page 96).
Displays the time interval for which the dynamic device parameters
are stored in the non-volatile memory.
The time interval displayed relates to storage of the following
dynamic device parameters:
• OUT
• PV
• FIELD_VAL
Note!
Since PROline Prosonic Flow 93 FF does not store the dynamic
device parameter in the non-volatile memory, this parameter always
1
displays the value 0
2 Resource Block
/
ms.
32
95