Foundation Fieldbus Parameters Of The Transducer Blocks - Endress+Hauser PROline Prosonic Flow 93 Function Manual

Foundation fieldbus ultrasonic flow measuring system
Hide thumbs Also See for PROline Prosonic Flow 93:
Table of Contents

Advertisement

3 Transducer Blocks (transmission blocks)
106
3.8
FOUNDATION Fieldbus parameters of the
Transducer Blocks
The following table provides you with a description of all the specified FOUNDATION
Fieldbus parameters of the Transducer Blocks. The E+H-specific parameters are
explained from Page 109 onwards.
FOUNDATION Fieldbus parameters (Transducer Blocks, transmission blocks)
Parameter
Write access
with operating
mode
(MODE_BLK)
ST_REV
read only
TAG_DESC
AUTO - OOS
STRATEGY
AUTO - OOS
ALERT_KEY
AUTO - OOS
PROline Prosonic Flow 93 FOUNDATION Fieldbus
Description
Displays the revision status of the static data.

Note!
The revision status parameter is incremented on each
modification of static data.
Entry of a user-specific text of max. 32 characters for unique
identification and assignment of the block.
Factory setting:
(_____) no text
Parameter for grouping and thus faster evaluation of blocks.
Grouping is carried out by entering the same numerical value in
the STRATEGY parameter of each individual block.
Factory setting:
0

Note!
These data are neither checked nor processed by the Transducer
Blocks.
Entry of the identification number of the plant unit.
This information can be used by the fieldbus host system for
sorting alarms and events.
User input:
1...255
Factory setting:
0