PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
PID function block (PID controller) / base index 810
Parameter
Write access
with operating
mode
(MODE_BLK)
LO_PRI
ROUT - RCAS -
CAS - AUTO -
MAN - OOS
6 PID function block (PID controller)
Description
Specifies the action taken when the lower warning limit value
(LO_LIM) is undershot.
User input:
0
The violation of the lower warning limit value is not evaluated.
1
No notification if the lower warning limit value is violated.
2
Reserved for block alarms.
3-7
The violation of the lower warning limit value is output as a user
notice with the appropriate priority (3 = low priority, 7 = high
priority).
8-15
The violation of the lower warning limit value is output as a critical
alarm with the appropriate priority (8 = low priority, 15 = high
priority).
Factory setting:
0
209