3 Transducer Blocks (transmission blocks)
158
"TRANSDUCER_DIAG" (E+H parameters) / base index 1600
Parameter
Write access
with operating
mode
(MODE_BLK)
System -
AUTO - OOS
Trouble-
shooting
System -
read
Operation
Time
T-DAT Save/
AUTO - OOS
Load
Amp. Device
read only
Family
PROline Prosonic Flow 93 FOUNDATION Fieldbus
Description
Use this parameter to rectify errors in the EEPROM. The EEPROM
is divided into a number of blocks. For fault elimination, select the
block in question and acknowledge the error.
Caution!
When you clear an error in a block, the parameters of the block
you select are reset to their factory settings.
Options:
CANCEL
MEASURED VALUES
SYSTEM UNITS
DENSITY PARAMETERS
QUICK SETUP
USER INTERFACE
TOTALIZER
COMMUNICATION
PROCESS PARAMETER
SYSTEM PARAMETER
SENSOR DATA
BATCH FUNCTION
ADVANCED DIAGNOSIS
AMPLIFIER PARAMETERS
SUPERVISION
VERSION INFO
SERVICE & ANALYSIS
PRODUCTION INFO
FILTER PARAMETER
Factory setting:
CANCEL
Displays the entire operation time (in seconds) since the flowmeter
was commissioned.
Use this parameter to save the parameter settings / configuration
of the transmitter in a transmitter DAT (T-DAT), or to load the
parameter settings from the T-DAT into the EEPROM.
Application examples:
• After commissioning, the current measuring point parameters
can be saved to the T-DAT as a backup.
• If the transmitter is replaced for some reason, the data from the
T-DAT can be loaded into the new transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from T-DAT to EEPROM)
Factory setting:
CANCEL
Note!
If the power supply fails, the totalizer readings are automatically
saved to the EEPROM.
This parameter is only used in the event of servicing.
Endress+Hauser
Need help?
Do you have a question about the PROline Prosonic Flow 93 and is the answer not in the manual?