PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
Base index: AI 1 = 350, AI 2 = 390, AI 3 = 430, AI 4 = 470, AI 5 = 510, AI 6 = 550, AI 7 = 590, AI 8 = 630
Parameter
Write access
with operating
mode
(MODE_BLK)
ALARM_SUM
AUTO - MAN -
OOS
ALERT_KEY
AUTO - MAN -
OOS
BLOCK_ALM
AUTO - MAN -
OOS
Analog Input function block /
Description
Displays the current status of the process alarms in the Analog
Input function block.
Display:
HI_HI_ALM
Violation of the upper limit value alarm
HI_ALM
Violation of the upper limit value warning
LO_LO_ALM
Violation of the lower limit value alarm
LO_ALM
Violation of the lower limit value warning
BLOCK ALM
Block alarm
Note!
In addition, the process alarms can also be disabled in this
parameter group.
Entry of the identification number of the plant unit.
This information can be used by the fieldbus host system for
sorting alarms and events.
User input:
1...255
Factory setting:
0
Displays the current block status with information on pending
configuration, hardware or system errors, including details of the
alarm time (date, time) when the error occurred.
The block alarm is triggered in the event of the following block
errors:
• SIMULATION ACTIVE
• INPUT FAILURE
• OUT OF SERVICE
• BLOCK CONFIG ERROR
Note!
If the option of the alarm has not been enabled in the
ACK_OPTION parameter, the alarm can only be acknowledged via
this parameter.
4 Analog Input function block
169