Resetting the Drive Following a Trip

PACMotion VFD has many protection features, designed to protect both the drive and motor from accidental
damage. When any of these protection features are activated, the drive will trip, and display a fault message.
The fault messages are listed in section Fault Messages on page 90.
When a trip occurs, after the cause of the trip has been investigated and rectified, the user can reset the trip
in one of the following ways:
• Press the keypad Stop key.
• Power off the drive completely, then power on again.
• If P1-13 > 0, switch off digital input 1, then back on again.
• If P1-12 = 4, reset via the fieldbus interface.
• If P1-12 = 6, reset via CAN.

Keypad Shortcuts

The following shortcuts can be used to speed up selecting and changing parameters when using the keypad.
Selecting the Parameter Groups
When extended or advanced parameter access is enabled (see section Extended Parameters on page 56),
additional parameter groups are visible, and may be selected quickly by the following method.
TFT and OLED Display :
Maximum frequency/Speed limit
P1-01
50 .0 Hz
Whilst in the parameter
selection menu, press
the Navigate and Up or
Navigate and Down keys
simultaneously.
Selecting the Lowest Parameter in a Group
TFT and OLED Display :
Motor rated current
P1-08
9 .5 A
Whilst in the parameter
selection menu, press
the Up and Down keys
simultaneously.
GFK-3111A
Preset frequency/Speed 1
P2-01
5 .0 Hz
The next highest or lowest
accessible parameter group
will be selected.
Maximum frequency/Speed limit
P1-01
50 .0 Hz
The next lowest accessible
parameter in the selected
parameter group will be
selected.
PACMotion VFD AC Variable Speed Drive User Guide
43