3-9 Parameter List
Parameter
Function name
No.
Multi-function output
C031
terminal 11 contact
selection
Multi-function output
C032
terminal 12 contact
selection
3
Multi-function output
C033
terminal 13 contact
selection
Multi-function output
C034
terminal 14 contact
selection
Multi-function output
C035
terminal 15 contact
selection
Relay output (AL2,
C036
AL1) contact
selection
Light load signal
C038
output mode
Light load detection
C039
level
Overload warning
C040
signal output mode
Overload warning
C041
level
Arrival frequency
C042
during acceleration
Arrival frequency
C043
during deceleration
PID deviation
C044
excessive level
Arrival frequency
C045
during acceleration 2
Arrival frequency
C046
during deceleration 2
C052
PID FB upper limit
C053
PID FB lower limit
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-45
Monitor or data range
00: NO
01: NC
00: NO contact at AL2; NC contact at AL1
01: NC contact at AL2; NO contact at AL1
00: ACC/DEC/CST (Enabled during
acceleration/deceleration/constant
speed)
01: Const (Enabled only during constant
speed)
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
00: ACC/DEC/CST (Enabled during
acceleration/deceleration/constant
speed)
01: Const (Enabled only during constant
speed)
0.0: Does not operate.
0.1 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.1 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.00 to 400.00
0.00 to 400.00
0.0 to 100.0
0.00 to 400.00
0.00 to 400.00
0.0 to 100.0
0.0 to 100.0
Changes
Default
during
Unit
Page
setting
operation
00
No
4-96
01
01
No
4-106
Rated
No
A
current
01
No
4-49
Rated
No
A
current
0.00
No
Hz
4-98
0.00
No
Hz
3.0
No
%
4-31
0.00
No
Hz
4-98
0.00
No
Hz
100.0
No
%
4-31
0.0
No
%