Frequency Jump Function; Acceleration Stop Function - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

Frequency Jump Function

•The frequency jump function helps avoid resonant points of loaded machines.
Parameter No.
Function name
A063
Jump frequency 1
A065
Jump frequency 2
A067
Jump frequency 3
A064
Jump frequency width 1
A066
Jump frequency width 2
A068
Jump frequency width 3
Related functions
•You cannot set output frequencies within a jump frequency setting range, where the frequency
jump function avoids steady operation.
•The output frequency fluctuates continuously according to the acceleration/deceleration time
during both actions.
You can set up to three points for the jump frequency.
Output frequency

Acceleration Stop Function

•When the moment of inertia of a machine load is large, this function delays acceleration until the
motor starting slip is reduced.
Use this function, if an overcurrent trip occurs during startup.
•Does not depend on acceleration pattern selection A097, and works with all acceleration patterns.
Parameter No.
Function name
A069
Acceleration stop frequency
A070
Acceleration stop time
0.00 to 400.00
0.00 to 10.00
A067
A065
A064
A063
A064
0.00 to 400.00
0.0 to 60.0
Output frequency
A069
A070
Data
Default setting
0.00
0.50
C001 to C008
A068
A068
A066
A066
Frequency reference
Data
Default setting
Frequency reference
4-2 Function Mode
Unit
Hz
Unit
0.00
Hz
0.0
s
4-30
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents