Register
Function name
No.
1348h
Not used
Analog operation level at
1349h
O disconnection
Analog operation level at
134Ah
OI disconnection
Analog operation level at
134Bh
O2 disconnection
134Ch
to
Not used
1350
1351h
Integrated power clear
Integrated power display
1352h
gain
1353h
Not used
1354h
Not used
1355h
Starting frequency
1356h
Carrier frequency
1357h
Initialization selection
Initialization parameter
1358h
selection
Frequency conversion
1359h
coefficient
135Ah
STOP key selection
135Bh
Free-run stop selection
Automatic carrier
135Ch
reduction
Usage rate of regenerative
135Dh
braking function
135Eh
Stop selection
135Fh
Cooling fan control
1360h
Not used
1361h
Not used
Function
R/W
Monitor and setting parameters
code
b070
R/W
0 to 100/no (ignored)
b071
R/W
0 to 100/no (ignored)
b072
R/W
-100 to 100/no (ignored)
Cleared with the Enter key after changing
b078
R/W
to 01
b079
R/W
1 to 1000
b082
R/W
0.10 to 9.99
0.5 to 15.0 (0.4 to 55 kW)
b083
R/W
0.5 to 10.0 (75 to 132 kW)
00: no (Clears the trip monitor)
01: Trip data (Initializes data)
02: Parameters (Clears the trip monitor
and initializes data)
b084
R/W
03: Trip+Param (Clears the trip monitor
and parameters)
04: Trp+Prm+EzSQ (Clears the trip moni-
tor, parameters and Drive Program)
01
b085
R/W
*Do not change.
b086
R/W
0.1 to 99.9
00: ON (Enabled)
01: OFF (Disabled)
b087
R/W
02: Only RESET (Disabled only during
stop)
00: 0-Hz start
01: f-match (Frequency matching start)
b088
R/W
02: Actv. f-match (Active Frequency
Matching restart)
00: OFF (Disabled)
b089
R/W
01: ON (Enabled)
b090
R/W
0.0 to 100.0
00: Decel-Stop (Deceleration  Stop)
b091
R/W
01: Free-RUN (Free-run stop)
00: Alws-ON (Always ON)
b092
R/W
01: ON in RUN (ON during RUN)
4-4 Communication Function
Resolu-
tion
1 [%]
1 [%]
1 [%]
4
1
0.01
[Hz]
0.1 [kHz]
0.1
0.1 [%]
4-198