Pid Control; Avr; Run Mode, Acceleration/Deceleration Functions - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

3-9 Parameter List
Parameter
Function name
No.
A071
PID selection
A072
PID P gain
A073
PID I gain
3
A074
PID D gain
A075
PID scale
PID feedback
A076
selection
A077
Reverse PID function
PID output limit
A078
function
PID feedforward
A079
selection
A081
AVR selection
AVR voltage
A082
selection
A085
RUN mode selection
Energy-saving
A086
response/accuracy
adjustment
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-29
Monitor or data range
00: OFF (Disabled)
01: ON (+) (Enabled)
02: ON (+/-) (Reverse output enabled)
0.2 to 5.0
0.0 to 3600.0
0.00 to 100.00
0.01 to 99.99
00: OI
01: O
02: Modbus (RS485 communication)
03: Pulse (Pulse train frequency)
10: Math (Operation function output)
00: OFF (Deviation = Target value -
Feedback value)
01: ON (Deviation = Feedback value - Target
value)
0.0 to 100.0
00: Disabled
01: O
02: OI
03: O2
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
00: Normal operation
01: Energy-saving operation
02: Automatic operation
0.0 to 100.0
Changes
Default
during
Unit
Page
setting
operation
00
No
1.0
Yes
1.0
Yes
s
0.00
Yes
s
1.00
No
Time
4-31
00
No
00
No
0.0
No
%
00
No
4-31
02
No
4-35
200/
No
V
400
00
No
4-36
50.0
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents