Omron 3G3RX User Manual page 95

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

Parameter
Function name
No.
Selection of non-stop
function at
b050
momentary power
interruption
Starting voltage of
non-stop function at
b051
momentary power
interruption
Stop deceleration
level of non-stop
b052
function at
momentary power
interruption
Deceleration time of
non-stop function at
b053
momentary power
interruption
Deceleration starting
width of non-stop
b054
function at
momentary power
interruption
Proportional gain
setting of non-stop
b055
function at
momentary power
interruption
Integral time setting
of non-stop function
b056
at momentary power
interruption
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Monitor or data range
00: OFF (Disabled)
01: V-Cnst (STOP) (Enabled (deceleration
stop))
02: NS1 (Enabled (without recovery))
03: NS2 (Enabled (with recovery))
0.0 to 1000.0
0.0 to 1000.0
0.01 to 3600.00
0.00 to 10.00
0.00 to 2.55
0.000 to 65.535
3-9 Parameter List
Changes
Default
during
Unit
Page
setting
operation
00
No
220/
No
V
440
360/
No
V
720
4-60
1.00
No
s
0.00
No
Hz
0.20
Yes
0.100
Yes
s
4-63
3-36
3