4-2 Function Mode

Reverse Rotation Prevention Function

•This function is enabled when "03" (sensorless vector control), "04" (0-Hz sensorless vector
control), or "05" (sensor vector control) is selected in control method A044/A244.
•Because of the Inverter's control characteristics, the Inverter may output a rotation signal in the
direction opposite to that of the RUN command (e.g. in a low-speed range). If the motor's reverse
rotation may cause a problem (e.g. damage to the machine driven by the motor), set reverse
rotation prevention selection b046 to "enabled".
Parameter No.
A044/A244
4
b046

Torque LADSTOP Function

•If "03" (sensorless vector control), "04" (0-Hz sensorless vector control), or "05" (sensor vector
control) is selected in control method A004/A244, this function temporarily stops the frequency
deceleration function (LAD) when the torque limit function is activated.
Parameter No.
A044/A244
b040
b041
b042
b043
b044
b045
C001 to C008
4-59
Function name
03: SLV (Sensorless vector control)
V/f characteristics
04: 0SLV (0-Hz sensorless vector control)
selection
05: V2 (Sensor vector control)
Reverse rotation
00: OFF (Disabled)
prevention selection
01: ON (Enabled)
Function name
03: SLV (Sensorless vector control)
V/f characteristics
04: 0SLV (0-Hz sensorless vector control)
selection
05: V2 (Sensor vector control)
00: 4-quadrant (Four-quadrant separate
01: TRQ input (Terminal switch)
Torque limit selection
02: [O] input (Analog input)
03: Option 1
04: Option 2
0 to 200 (0.4 to 55 kW)
Torque limit 1
0 to 180 (75 to 132 kW)
(Four-quadrant mode
no (Torque limit disabled)
forward power running)
Forward power running
under four-quadrant separate setting
0 to 200 (0.4 to 55 kW)
Torque limit 2
0 to 180 (75 to 132 kW)
(Four-quadrant mode
no (Torque limit disabled)
reverse regeneration)
Reverse regeneration
under four-quadrant separate setting
0 to 200 (0.4 to 55 kW)
Torque limit 3
0 to 180 (75 to 132 kW)
(Four-quadrant mode
no (Torque limit disabled)
reverse power running)
Reverse power running
under four-quadrant separate setting
0 to 200 (0.4 to 55 kW)
Torque limit 4
0 to 180 (75 to 132 kW)
(Four-quadrant mode
no (Torque limit disabled)
forward regeneration)
Forward regeneration
under four-quadrant separate setting
Torque LADSTOP
00: OFF (Disabled)
selection
01: ON (Enabled)
40: TL (Torque limit enabled)
Multi-function inputs
41: TRQ1 (Torque limit switching 1)
1 to 8 selection
42: TRQ2 (Torque limit switching 2)
Data
Data
setting)
Default setting
Unit
00
00
Default setting
Unit
00
00
150
%
00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents