Operator Rotation Direction Selection - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

4-2 Function Mode
•The set time here indicates the acceleration/deceleration time from 0 Hz to the maximum
frequency.
4
•When the LAD cancel (LAC) function is selected in the multi-function input selection and the signal
is turned on, the acceleration/deceleration time is ignored, and the output frequency
instantaneously follows the reference frequency.
•To switch between the 1st/2nd/3rd acceleration times or between the 1st/2nd/3rd deceleration
times, allocate 08 (SET)/17 (SET3) to the desired multi-function input (refer to "Multi-function Input
Selection" (page 4-79)), and use the SET/SET3.
•You can set the acceleration/deceleration time via (1) the Digital Operator, (2) optional board 1, or
(3) optional board 2.
•Even if a short acceleration/deceleration time is set, the actual time cannot be shorter than the
minimum acceleration/deceleration time that is determined by the mechanical inertia moment and
the motor torque. If you set a time shorter than the minimum time, an overcurrent/overvoltage trip
may occur.
Acceleration Time T
(
J
L
T
=
S
9.55
Deceleration Time T
(
J
L
T
=
B
9.55
For short-time deceleration, use a braking unit (optional).

Operator Rotation Direction Selection

•Select the rotation direction applied to the RUN command via the Digital Operator.
•This is disabled at terminals.
Parameter No.
F004
4-9
Output frequency
Max. frequency
A004/A204/A304
Actual
acceleration
time
F002/F202/F302
S
)
J
N
+
M
M
(
)
T
T
S
L
B
J
)
N
+
M
M
(
)
T
T
+
B
L
Function name
Operator rotation direction
selection
Output frequency set value
Actual
deceleration
time
F003/F203/F303
J
: Inertia moment of the load converted to the motor shaft [kg·m
L
J
: Inertia moment of the motor [kg·m
M
N
: Motor rotation speed [r/min]
M
T
: Max. acceleration torque with the Inverter driving [N·m]
S
T
: Max. deceleration torque with the Inverter driving [N·m]
B
T
: Required driving torque [N·m]
L
Data
00: FWD (Forward)
01: REV (Reverse)
2
]
2
]
Default setting
Unit
00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents