4-4 Communication Function
Register
No.
1319h
Overload limit selection 2
4
131Ah
Overload limit level 2
131Bh
Overload limit parameter 2
Overcurrent suppression
131Ch
function
Active Frequency
131Dh
Matching restart level
Active Frequency
131Eh
Matching restart
parameter
Starting frequency at
131Fh
Active Frequency
Matching restart
1320h
Soft lock selection
1321h
Not used
1322h
Not used
1323h
RUN time/Power ON time
setting
1324h
Rotation direction limit
1325h
selection
Reduced voltage startup
1326h
selection
4-195
Function
Function name
code
b024
b025
b026
b027
b028
b029
b030
b031
b034
(HIGH)
b034
(LOW)
b035
b036
R/W
Monitor and setting parameters
00: OFF (Disabled)
01: ON-Acc/Cnst (Enabled in
acceleration/constant speed
operation)
R/W
02: ON-Cnst (Enabled during constant
speed operation)
03: ON-A/C (R) (Enabled in acceleration/
constant speed operation
(accelerates during regeneration))
0.20 x Rated current to 2.00 x Rated
current (0.4 to 55 kW)
R/W
0.20 x Rated current to 1.80 x Rated
current (75 to 132 kW)
R/W
0.10 to 30.00
00: OFF (Disabled)
R/W
01: ON (Enabled)
0.20 x Rated current to 2.00 x Rated
current (0.4 to 55 kW)
R/W
0.20 x Rated current to 1.80 x Rated
current (75 to 132 kW)
R/W
0.10 to 30.00
00: Off FQ (Frequency at interruption)
R/W
01: Max.FQ (Max. frequency)
02: Set FQ (Set frequency)
00: Lock (SFT) (Data other than b031
cannot be changed when terminal
SFT is ON)
01: Only FQ (SFT) (Data other than b031
and the specified frequency parame-
ter cannot be changed when terminal
SFT is ON)
R/W
02: Lock (Data other than b031 cannot be
changed)
03: Only FQ (Data other than b031 and
the specified frequency parameter
cannot be changed)
10: RUN chg mode (Data other than pa-
rameters changeable during opera-
tion cannot be changed)
R/W
0 to 65535
R/W
00: FREE (Forward and Reverse are
enabled)
R/W
01: FWD (Only Forward is enabled)
02: REV (Only Reverse is enabled)
0: (Reduced voltage startup time: Short)
R/W
to 255: (Reduced voltage startup time:
Long)
Resolu-
tion
0.1 [A]
0.01 [s]
0.1 [A]
0.01 [s]
1 [h]