4-1 Monitor Mode
4Functions
4-1 Monitor Mode

Output Frequency Monitor [d001]

Displays the set point of output frequency of the Inverter afected by acceleration and deceleration
ramps but without compensations. During stop, "0.00" is displayed.
(Display)
0.00 to 400.00
4
Note: When the frequency reference is set using the Digital Operator, the output frequency can be
Note: This will correspond with the theoretical motor speed but not with the real output frequency of

Output Current Monitor [d002]

Displays the output current value of the Inverter. During stop, "0.00" is displayed.
(Display)
0.0 to 9999.0: Displays in increments of 0.1 A.
Rotation Direction Monitor [d003]
Displays the RUN direction of the Inverter.
The RUN LED indicator lights up during forward/reverse rotation.
(Display)
FWD: Forward
STOP: Stop
REV: Reverse
PID Feedback Value Monitor [d004]
When "Enabled" (01) or "Reverse output enabled" (02) is selected in PID selection A071, the PID
feedback value can be monitored.
Gain conversion is enabled with PID scale A075.
"d004 display" = "PID feedback value (%)" × "PID scale (A075)"
(A075): 0.01 to 99.99 (Can be set in increments of 0.01.)
(Display)
0.00 to 999000.00: Displays in increments of 0.01.
4-1
: Displays in increments of 0.01 Hz.
changed with the Increment/Decrement key during operation only.
The frequency setting changed with this monitor will be reflected in frequency reference F001.
Pressing the Enter key overwrites the currently selected frequency reference.
the inverter.