Daily Inspection And Periodic Inspection - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

6-1 Inspection and Maintenance
Daily Inspection and Periodic Inspection
Inspection
Inspection
part
item
Ambient
environment
General
Entire device
Power
6
supply
voltage
Main
General
circuit
*1. The life of the smoothing capacitor depends on ambient temperature.
Refer to "Appendix-2 Product Life Curve" for the replacement reference.
*2. The life of the cooling fan varies depending on the environmental conditions, such as ambient temperature
and/or dust. Check the operation through daily inspections.
*3. The replacement reference (year/cycle) or "
life, which is not guaranteed.
6-3
Inspection period
Inspection point
Periodic
Daily
1 year 2 years
Check ambient
temperature, as
well as humidity
and dust levels.
Check that there
are no abnormal
vibrations or
sounds.
Check that the
main circuit
voltage is normal.
Megger check
(between main
circuit terminal
and ground
terminal)
Appendix-2 Product Life Curve
Inspection method
Criteria
Ambient
temperature
10C to 50C,
Refer to "2-1
no freezing.
Installation".
Ambient
humidity 90%
max., no
condensation.
Visual or acoustic
No faults
inspection
Measure the voltage
Must be within
between Inverter
allowable
main circuit terminals
fluctuation of
R/L1, S/L2, and T/L3.
AC voltage.
Disconnect the I/O
wirings of the Inverter
main circuit terminal
block, detach the
control terminal block
board, and remove
the short-circuit bar
used for switching the
Inverter built-in filter
function. Then, use a
5 M min.
megger to measure
the resistance
between the ground
terminal and the
short-circuited parts
of terminals R/L1, S/
L2, T/L3, U/T1, V/T2,
W/T3, P/+, PD/+1,
N/-, RB, Ro, and To.
" is based on the expected design
Meter
Thermomet
-er
Hygrometer
Recorder
Tester,
digital
multimeter
500 V DC
megger