Special Reduced Torque Characteristics (Special VP)
Suitable for a fan or pump that requires torque in a low speed range. These have VC characteristics
only for low deceleration in reduced torque characteristics.
Period a: Provides constant torque characteristics within a range from 0 Hz to 10% of the base
frequency.
(Example) If the base frequency is 50 Hz, the Inverter provides constant torque
characteristics within a range from 0 to 5 Hz.
Period b: Provides reduced torque characteristics within a range from 10% to 100% of the base
frequency.
The Inverter outputs voltage based on a curve of the 1.7th power of the frequency.
Period c: Provides constant voltage characteristics within a range from the base frequency to the
maximum frequency.
Free V/f Setting
•You can set desired V/f characteristics by setting 7 points of voltage and frequency. (b100 to b113)
•The free V/f frequencies should always be 1  2  3  4  5  6  7.
All the default settings are 0 Hz. You must set Free V/f setting 7 first. (Operation is disabled by
factory default.)
•If the free V/f setting is enabled, the functions of torque boost A041/A241, base frequency A003/
A203/A303, and maximum frequency A004/A204/A304 are disabled. (Free V/f frequency 7 is
regarded as the maximum frequency.)
Parameter No.
Function name
b100
Free V/f frequency 1
b102
Free V/f frequency 2
b104
Free V/f frequency 3
b106
Free V/f frequency 4
b108
Free V/f frequency 5
b110
Free V/f frequency 6
b112
Free V/f frequency 7
b101
Free V/f voltage 1
b103
Free V/f voltage 2
b105
Free V/f voltage 3
b107
Free V/f voltage 4
b109
Free V/f voltage 5
b111
Free V/f voltage 6
b113
Free V/f voltage 7
Related functions
Output
voltage
(100%)
1.7
VP(f )
VC
0
10% of base
Base
frequency
frequency
a
c
b
Data
0 to Free V/f frequency 2
0 to Free V/f frequency 3
0 to Free V/f frequency 4
0 to Free V/f frequency 5
0 to Free V/f frequency 6
0 to Free V/f frequency 7
0 to 400
0.0 to 800.0
4-2 Function Mode
Output
frequency (Hz)
Max.
frequency
Description
Set frequencies for
each break point.
Set output voltages
*
for each break point.
A044, A244, A344
Default setting
Unit
0
Hz
0.0
V
4-22