RUN Time/Power ON Time Exceeded

•If the total RUN time of the Inverter exceeds the time set in ON time setting b034, a RUN/Power
ON 'time exceeded' (RNT/ONT) signal is output.
Parameter No.
Function name
RUN time/Power ON
b034
time setting
Related functions
RUN Time Exceeded (RNT)
•Allocate 11 (RNT) to any of multi-function output terminals 11 to 15 (C021 to C025) or the relay
output terminal (C026).
•Set a time in RUN time/Power ON time setting b034.
Power ON Time Exceeded (ONT)
•Allocate 12 (ONT) to any of multi-function output terminals 11 to 15 (C021 to C025) or the relay
output terminal (C026).
•Set a time in RUN time/Power ON time setting b034.

Rotation Direction Limit Selection

•Limits motor rotation directions.
•Enabled in either "control circuit terminal block" or "Digital Operator" control mode.
Parameter No.
Function name
Rotation direction limit
b035
selection
Data
0 to 65535
C021 to C025, C026, d016, d017
Data
00: FREE (Forward and Reverse are
enabled)
01: FWD (Only Forward is enabled)
02: REV (Only Reverse is enabled)
4-2 Function Mode
Default setting
Unit
0
Default setting
Unit
00
4-52