Parameter Initialization - Omron 3G3RX User Manual

Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

3-6 Test Run Operation

Parameter Initialization

•Initialize the parameters using the following procedure.
•To initialize the parameters, set parameter b084 to "2" and parameter b180 to "1".
Key sequence
3
3-15
Display example
MONITOR-A
M1-STOP ALL
d001 Output FQ
Power On
0.00Hz
F001
0.00Hz
FUNCTION
M1-STOP ALL
F001
Press the Prev. Page or Next Page key until function mode is
Set Frequency (TM)
displayed.
0 .00Hz
[0.00 – 50.00]
FUNCTION
M1-STOP ALL
F
001
Press the Set key to enter function mode.
Set Frequency (TM)
0 .00Hz
[0.00 – 50.00]
FUNCTION
M1-STOP ALL
b
084
With the Prev. Page, Next Page, Up and Down keys write the
Initialize Mode
parameter b084.
00:no
[00 – 04]
FUNCTION
M1-STOP ALL
b084
Press the Set key to enter b084 parameter.
Initialize Mode
00
:no
[00 – 04]
FUNCTION
M1-STOP ALL
b084
With the Prev. Page, Next Page, Up and Down keys put the
Initialize Mode
parameter b084 to 2.
02
:Parameters
[00 – 04]
FUNCTION
M1-STOP ALL
b0
84
Press the Set key to change the parameter b084 to 2.
Initialize Mode
02
:Parameters
[00 – 04]
FUNCTION
M1-STOP ALL
b
180
With the Prev. Page, Next Page, Up and Down keys write the
Initialize trigger
parameter b180.
00:No action
[00 – 01]
FUNCTION
M1-STOP ALL
b
180
Press the Set key to enter b180 parameter.
Initialize trigger
00
:No action
[00 – 01]
Description

Hide quick links:

Advertisement

Table of Contents
loading