Appendix-1 Parameter List
Extended Function Mode
Parameter
Function name
No.
Frequency reference
A001
selection
[Frequency source]
RUN command
A002
selection
[RUN cmd source]
Base frequency
A003
[Base Frequency]
* 2nd set base
A203
frequency
[Base Frequency-M2]
* 3rd set base
A303
frequency
[Base Frequency-M3]
Maximum frequency
A004
[Max.Frequency]
* 2nd maximum
A204
frequency
[Max.Frequency-M2]
* 3rd maximum
A304
frequency
[Max.Frequency-M3]
O/OI selection
A005
[AT Select]
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
App-5
Monitor or data range
00: VR (Digital Operator (FREQ adjuster))
(Enabled when 3G3AX-OP01 is used.)
01: Terminal
02: Digital Operator (F001)
03: RS485 (ModBus communication)
04: Option 1
05: Option 2
06: Pulse train frequency
07: EzSQ (Drive programming)
10: (Math) Operation function result
01: Terminal
02: Digital Operator (F001)
03: RS485 (ModBus communication)
04: Option 1
05: Option 2
30 to Maximum frequency [A004]
30 to 2nd maximum frequency [A204]
30 to 3rd maximum frequency [A304]
A003 to 400
A203 to 400
A303 to 400
00: [O]/[O2] Switches between O/OI terminal
AT
01: [O]/[O2] Switches between O/O2 terminal
AT
02: [O]/VR Switches between O/FREQ
adjuster via terminal AT
(Enabled only when 3G3AX-OP01 is
used)
03: [OI]/VR Switches between OI/FREQ
adjuster via terminal AT
(Enabled only when 3G3AX-OP01 is
used)
04: [O2]/VR Switches between O2/FREQ
adjuster via terminal AT
(Enabled only when 3G3AX-OP01 is
used)
Changes
Default
during
Unit
Page
setting
operation
4-10
01
No
4-144
01
No
4-11
4-11
50
4-112
50
No
Hz
4-11
50
50
50
No
Hz
4-12
50
00
No
4-12