Maximum Frequency

•Set the maximum value of the output frequency.
•The value set here is the maximum value (e.g.,10 V in the range from 0 to 10 V) of the external
analog input (frequency reference).
•The maximum Inverter output voltage from base to maximum frequencies is the voltage set in AVR
voltage selection A082.
•The Inverter cannot output voltage beyond that of the incoming voltage.
Parameter No.
Function name
A004
Maximum frequency
A204
*2nd maximum frequency
A304
*3rd maximum frequency
Related functions
* To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it
on.

Analog Input (O, O2, OI)

•The Inverter has three types of external analog input terminals.
O-L terminal: 0 to 10 V
OI-L terminal: 4 to 20 mA (current input)
O2-L terminal: -10 to 10 V (voltage input)
•Below are the settings for this function.
Parameter No.
Function name
A005
O/OI selection
A006
O2 selection
Related functions
Output voltage
AVR voltage
selection
(A082)
Base frequency
30 to 400
(voltage input)
Data
00: [O]/[O2] Switches between O/OI terminal AT
01: [O]/[O2] Switches between O/O2 terminal AT
02: [O]/VR Switches between O/FREQ adjuster
via terminal AT (Enabled only when 3G3AX-
OP01 is used.)
03: [OI]/VR Switches between OI/FREQ adjuster
via terminal AT (Enabled only when 3G3AX-
OP01 is used.)
04: [O2]/VR Switches between O2/FREQ
adjuster via terminal AT (Enabled only when
3G3AX-OP01 is used.)
00: [O2] only
01: [O/OI-P] Auxiliary frequency reference
(not reversible)
02: [O/OI-PM] Auxiliary frequency reference
(reversible)
03: [OFF] O2 disabled
A005, A006, C001 to C008
4-2 Function Mode
Max. frequency
Data
Default setting
A003, A203, A303, A081, A082
Default setting
Unit
50
Hz
Unit
00
03
4-12
4