Electrical Ratings (230V Build Variant) - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

9-6
Technical Specifications

Electrical Ratings (230V Build Variant)

Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Operation at 208V 10% (Frames C, D, E & F)
Nominal motor powers are reduced by 10% when operated at 208V 10%. Output currents
remain unchanged.
Model Number
FRAME C : Input currents for kW ratings are at 230V 50Hz ac input. Supply short circuit rating 10kA.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232220-..
650G-232280-..
Normal Duty (Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232220-..
650G-232280-..
FRAME D : Input currents for kW ratings are at 230V 50Hz ac input. Supply short circuit rating 10kA.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232420-..
650G-232540-..
650G-232680-..
Normal Duty (Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232420-..
650G-232540-..
650G-232680-..
FRAME E : Input currents for kW ratings are at 230V 50Hz ac input. Prospective short circuit current 18kA.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-232800-..
Normal Duty (Output Overload Motoring 110% for 30s, 130% for 0.5s short term rating)
650G-232800-..
FRAME F : Input currents for kW ratings are at 230V 50Hz ac input. Prospective short circuit current 18kA.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-233104-..
650G-233130-..
650G-233154-..
Normal Duty (Output Overload Motoring 110% for 30s, 125% for 0.5s short term rating)
650G-233104-..
650G-233130-..
650G-233154-..
Power Supply = 220-240V ±10%, 45-60Hz
Motor
Power
5.5kW
7.5Hp
5.5kW
10Hp
7.5kW
10Hp
11kW
15Hp
11kW
15Hp
15kW
20Hp
18.5kW
25Hp
15kW
20Hp
18.5kW
25Hp
All values are the same as for Heavy Duty except for changes described by
parameter
22kW
30Hp
30kW
40Hp
30kW
40Hp
37kW
50Hp
45kW
60Hp
37kW
50Hp
45kW
60Hp
55kW
75Hp
www.comoso.com
Output
Input
Heatsink
Current
Current
Power
(A)
(A)
Loss
(W)
22
25
270
22
25
270
28
33
290
28
33
290
28
31
330
28
31
330
42
49.3
500
42
49.3
500
42
45
570
42
45
570
54
53
670
54
53
670
68
65
850
68
65
850
54
54
750
54
54
750
68
65
850
68
65
850
P
12. Refer to Chapter 6 : "Programming Your Application"
80
91
800
80
91
800
104
116
1050
104
116
1050
104
102
850
104
102
850
130
126
1100
130
126
1100
154
148
1200
154
148
1200
130
126
1150
130
126
1150
154
148
1350
154
148
1350
192
184
1600
192
184
1600
Total
Maximum
Input
Power
Switching
Bridge I
Loss
Frequency
(A
2
s)
(W)
(kHz)
330
3
4000
330
3
4000
350
3
6000
350
3
6000
390
3
4000
390
3
4000
560
3
6000
560
3
6000
640
3
6000
640
3
6000
740
3
6000
740
3
6000
920
3
6000
920
3
6000
820
3
6000
820
3
6000
920
3
6000
920
3
6000
920
3
18000
920
3
18000
1200
3
18000
1200
3
18000
1100
3
100000
1100
3
100000
1450
3
100000
1450
3
100000
1650
3
100000
1650
3
100000
1500
3
100000
1500
3
100000
1800
3
100000
1800
3
100000
2100
3
100000
2100
3
100000
650G AC Drive