Power Terminal Description

Terminal
Description
TH1A
Thermistor
TH1B
Thermistor
Reference
Terminal
L1 *
Power Input
L2/N *
Power Input
L2
L3
Power Input
DC-
Power Input
DC+
Power Input/
Dynamic
Brake
DBR
Dynamic
Brake
M1/U
Motor
M2/V
Outputs
M3/W
Reference
Terminal

Terminal Block Acceptance Sizes

Wire sizes for Europe should be chosen with respect to the operating conditions and your local National
Electrical Safety Installation Requirements. Local wiring regulations always take precedence. For North
American UL wire sizes refer to Chapter 10: "Certification for the Drive" - Requirements for UL
Compliance.
Product Code
Frame 1 - 2
Frame 3
Frame C
Frame D (15-22kW)
Frame D (30/18.5kW)
Frame E
Frame F
Note: The standard Frame E and Frame F terminals are not intended for flat busbar. A Power Terminal adaptor is
available to enable wiring with flat busbar, part number BE465483.
* The larger wire sizes can be used provided a crimp is fitted to the wire
650G AC Drive
Function
Connection to motor
It is good practice to protect motors by fitting temperature
thermistor
sensitive resistors. A typical resistance (up to a reference
Connection to motor
temperature of 125C) is 200, rising rapidly to 2000 above
thermistor
this temperature. Connect devices in series between TH1A and
TH1B. Link the terminals if temperature sensors are not used.
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
Single and three
220/240V ac ±10%
phase live
rms with respect to
connection
L2/N. 50-60Hz (IT/TN)
Single phase neutral
220/240V ac ±10%
(or L2 three phase
with respect to L1. 50-
live connection)
60Hz (IT/TN)
Three phase live
Not applicable
connection
Common bus supply Not applicable
Common bus
Not applicable
supply/external
brake resistor
Connection to
Not applicable
external brake
resistor
Connection for
Motor rated at:
motor
0 to 220/240V ac
0 to 240Hz
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
Power Terminals
(minimum/maximum acceptance for aperture)
0.75 mm
2
/ 2.5 mm
6.0 mm
2
/ 2.5 mm
0.75 mm
2
/ 10mm
2.5 mm
2
/ 16mm
2.5 mm
2
/ 25mm
Solid
16 mm
2
/ 50mm
2
2
2
25 mm
/120mm
www.comoso.com
Installing the Drive
Range
200V 1-Phase
220/240V or 380/460V ac ±10%
rms with respect to L2, L3 phase-to-
phase. 50-60Hz (IT/TN)
220/240V or 380/460V ac ±10%
with respect to L1, L3. 50-60Hz
(IT/TN)
220/240V or 380/460V ac ±10%
with respect to L1, L2. 50-60Hz
(IT/TN)
See "Internal Dynamic Brake Switch"
table
See "Internal Dynamic Brake Switch"
table
Motor rated at:
0 to 220/240V or 0 to 380/460V ac
0 to 240Hz
2
12AWG
2
10AWG
2
(*16mm
2
)
2
(* 25mm
2
)
2
(* 35mm
2
)
Stranded
25 mm
2
/ 50mm
2
(* 70mm
2
2
2
35 mm
/ 95mm
(*120mm
3-18
200V/400V 3-Phase
Control Terminals
including Thermistor Terminals
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
)
2.5 mm
2
2
2
)
2.5 mm