Electrical Ratings (400V Build Variant)

Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Model Number
FRAME C : Input currents for kW ratings are at 400V 50Hz ac input, and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 10kA.
* For UL Listed products rated at 15kW/20Hp, a supply voltage of 460V is required. The higher
current ratings are applicable to non UL applications only.
Heavy Duty (Output Overload Motoring 150% for 30s, 180 % for 0.5s short term rating)
650G-432160-..
650G-432230-..
650G-432300-..
Normal Duty (Output Overload Motoring 110% for 30s)
650G-432160-..
650G-432230-..
650G-432300-..
FRAME D : Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac
input. Prospective short circuit current 10kA.
* For UL Listed products rated at 30kW/40Hp, a supply voltage of 460V is required. The higher
current ratings are applicable to non UL applications only.
Heavy Duty (Output Overload Motoring 150% for 30s, 180% for 0.5s short term rating)
650G-432310-..
650G-432380-..
650G-432450-..
650G-432590-..
Normal Duty (Output Overload Motoring 110% for 30s)
650G-432310-..
650G-432380-..
650G-432450-..
650G-432590-..
650G AC Drive
Power Supply = 380-460V ±10%, 50/60Hz 5%
Motor
Power
7.5kW
10Hp
11kW
15Hp
15kW
20Hp
11kW
15Hp
15kW
20Hp
18.5kW
25Hp
15kW
20Hp
18.5kW
25Hp
22kW
30Hp
30kW
40Hp
18.5kW
25Hp
22kW
30Hp
30kW
40Hp
37kW
50Hp
www.comoso.com
Technical Specifications
Output
Input
Heatsink
Current
Current
Power
(A)
(A)
Loss (W)
16
19
240
14
16
225
23
26.1
280
23
22.1
260
30
37
440
27
31.2
410
23
26.1
300
21
22.1
280
30
33.6
440
27
28.5
410
37
44
550
34
38
530
31
34.8
420
31
28.5
400
38
40.5
545
38
34.2
515
45
47.2
670
45
40
640
59
66
760
52
56
740
38
40.5
545
38
34.2
515
45
47.2
670
45
40
640
59
61
760
52
51
740
73
84
920
65
68
890
9-7
Total
Maximum
Input
Power
Switching
Bridge I
Loss
Frequency
(A
2
s)
(W)
(kHz)
290
3
4000
275
3
4000
330
3
4000
310
3
4000
500
3
6000
470
3
6000
350
3
4000
320
3
4000
500
3
4000
470
3
4000
610
3
6000
580
3
6000
480
3
4000
460
3
4000
605
3
6000
575
3
6000
730
3
6000
700
3
6000
860
3
15000
830
3
15000
605
3
4000
575
3
4000
730
3
6000
700
3
6000
860
3
6000
830
3
6000
1030
3
15000
980
3
15000
2
t