Parker 650G Product Manual page 148

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

13-7
Applications
Application 3: Preset Speeds
This is ideal for applications requiring multiple discrete speed levels.
The setpoint is selected from either the sum of the analogue inputs, (as in Application 1 and known here as PRESET 0), or
as one of up to seven other pre-defined speed levels. These are selected using DIN2, DIN3 and DIN4, refer to the Truth
Table below.
P
P
Edit parameters
302 to
308 on the keypad to re-define the speed levels of PRESET 1 to PRESET 7. Reverse direction is
achieved by entering a negative speed setpoint.
SINGLE
WIRE
STARTING
Speed Trim
A or V
Speed
default source
Setpoint
= 4-20mA
User Relay
Preset Speed Truth Table
Control
Terminal
13
13
DIN7 (ENCB)
not used
12
12
not used
DIN6 (ENCA)
11
11
DIN5
NOT COAST STOP
10
10
DIN4/DOUT2
PRESET SELECT 3
9
9
DIN3
PRESET SELECT 2
8
8
DIN2
PRESET SELECT 1
7
7
DIN1
RUN FORWARD
6
6
+24V
24V
5
5
AOUT
RAMP OUTPUT
4
4
+10V REF
+10V REF
3
3
AIN2
SPEED TRIM
2
2
AIN1
SPEED SETPOINT
1
1
0V
0V
RL1A
DOUT3 (relay)
RELAY SOURCE
RL1B
DIN4/DOUT2
0V
0V
0V
0V
24V
24V
24V
24V
www.comoso.com
24V = coast to stop, 0V = drive may run
see truth table below
see truth table below
see truth table below
24V = run forward
= 1
= 3
= 0
= 1
DIN3
DIN2
Preset
0V
0V
0V
24V
24V
0V
24V
24V
0V
0V
0V
24V
24V
0V
24V
24V
DEMAND (0V = 0%, 10V = 100%)
4mA = 0%, 20mA = 100% (Preset 0)
0V = 0%, 10V = 100% (Preset 0)
HEALTH i.e. 0V = not healthy
0
1
2
3
4
5
6
7