Terminal Tightening Torques - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

3-19
Installing the Drive

Terminal Tightening Torques

Frame Size
Product Code
(Block 2 & 3)
Frame 3
Frame C 400/500V
Frame D
Frame E
Frame F
Power Wiring
For specified EMC emission and immunity performance, install to EMC Installation
Note:
Instructions. Refer to Chapter 10: "Certification for the Drive" - for more information
Protect the incoming mains supply using the specified fuse, or RCD circuit breaker Type B.
IMPORTANT: We do not recommend the use of circuit breakers (e.g. RCD, ELCB, GFCI), however,
where their use is mandatory, they must:
Model Recognition
Thermistor
Catalog Code
(Block 2 & 3)
ALL
ALL
All
All
All
All
All
All
(6.1 lb-in)
All
All
(6.1 lb-in)
Operate correctly with dc and ac protective earth currents (i.e. type B RCDs as in
Amendment 2 of IEC755).
Have adjustable trip amplitude and time characteristics to prevent nuisance tripping
on switch-on.
www.comoso.com
Power
& fan
Terminals
supply
2.26Nm
N/A
(20 lb-in)
1.35Nm (12 lb-in)
enclosed terminal type
N/A
1.8Nm (16 lb-in)
open terminal type
4Nm
N/A
(35 lb-in)
0.7Nm
6-8Nm
(53-70 lb-in)
0.7Nm
15-20Nm
(132-177 lb-in)
Brake
Ground
Terminals
Terminals
2.26Nm
2.26Nm
(20 lb-in)
(20 lb-in)
1.35Nm
2.5Nm
(12 lb-in)
(22 lb-in)
4Nm
4.5Nm
(35 lb-in)
(40 lb-in)
6-8Nm
6-8Nm
(53-70 lb-in)
(53-70 lb-in)
0.7Nm
42Nm
(6.1 lb-in)
(375 lb-in)
650G AC Drive