Supply Harmonic Analysis (Frame E Normal Duty) - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

9-24
Technical Specifications

Supply Harmonic Analysis (Frame E Normal Duty)

Assumptions: 10000A short circuit supply capability
equivalent to 73H supply impedance at 400V
rated rms value of the fundamental voltage of the supply
transformer. The results conform to stage 1, stage 2 and stage
3 of the Engineering Recommendation G.5/3 September 1976,
Classification 'C': Limits for Harmonics in the UK Electricity
Industry.
Fundamental
230
Voltage (V)
Inverter Type
Motor Power
22.0
(kW)
Typical
Motor
90
Efficiency %
Harmonic
No.
1
102.1
3
0.1
5
49.1
7
21.7
9
0.0
11
6.3
13
4.1
15
0.0
17
2.8
19
1.7
21
0.0
23
1.6
25
1.0
27
0.0
29
1.0
31
0.7
33
0.0
35
0.7
37
0.5
39
0.0
40
0.0
41
0.5
42
0.0
43
0.4
44
0.0
45
0.0
46
0.0
47
0.3
48
0.0
49
0.3
50
0.0
Total RMS
115.6
Current (A)
THD (V) %
1.84
where Q
400
Three Phase
30.0
37.0
90
90
RMS Current (A)
64.3
74.8
0.1
0.1
41.9
48.7
26.0
30.3
0.0
0.0
4.4
5.0
4.0
4.6
0.0
0.0
2.3
2.7
1.6
1.8
0.0
0.0
1.4
1.6
0.9
1.1
0.0
0.0
0.8
1.0
0.6
0.7
0.0
0.0
0.5
0.6
0.5
0.5
0.0
0.0
0.0
0.0
0.4
0.4
0.0
0.0
0.3
0.4
0.0
0.0
0.0
0.0
0.0
0.0
0.2
0.3
0.0
0.0
0.2
0.3
0.0
0.0
81.3
94.6
2.98
3.46
www.comoso.com
,
is the
1n
THD(V) x 100 
45.0
30.0
90
90
89.1
51.5
0.1
0.1
55.2
35.4
32.2
23.3
0.0
0.0
5.1
5.1
5.9
3.3
0.0
0.0
2.5
2.6
2.3
1.5
0.0
0.0
1.5
1.4
1.2
1.0
0.0
0.0
1.0
0.7
0.8
0.7
0.0
0.0
0.7
0.4
0.6
0.4
0.0
0.0
0.0
0.0
0.5
0.3
0.0
0.0
0.4
0.3
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.2
0.0
0.0
0.4
0.2
0.0
0.0
110.0
67.1
3.84
1.52
h 2
 Q
h 2
%
h 40
Q
1n
500
37.0
45.0
90
90
63.6
75.5
0.0
0.0
43.1
48.9
28.0
30.1
0.0
0.0
5.7
5.4
4.1
5.1
0.0
0.0
3.0
2.8
1.8
2.0
0.0
0.0
1.6
1.6
1.2
1.1
0.0
0.0
0.9
1.0
0.8
0.7
0.0
0.0
0.6
0.6
0.6
0.5
0.0
0.0
0.0
0.0
0.4
0.4
0.0
0.0
0.4
0.4
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.3
0.0
0.0
0.3
0.3
0.0
0.0
82.2