6-5
Programming Your Application
MMI Parameters Table
Display
Parameter
SLIP COMP
ENABLE
VF
STABILISATION
ENABLE
VF
VOLTAGE
CONTROL MODE
VF
BOOST MODE
F VF
AUTO BOOST
F M VF
ENERGY SAVING
F VF
MOTOR
CURRENT
M SV
Description
Slip compensation is operational when TRUE.
Eliminates motor speed variations under load
conditions in V/F Fluxing Mode when the correct
value for MAG CURRENT is entered into
Enables the stabilisation function when TRUE.
Eliminates light load speed variations in V/F
Fluxing Mode
NONE : no attempt is made to control the PWM
modulation depth for variations in dc link voltage
FIXED : the drive's output volts are maintained,
regardless of variations in the dc link voltage. The
drive's product code sets the default value for
demanded maximum output voltage (see MOTOR
VOLTAGE below)
AUTOMATIC : the drive performs controlled over-
fluxing during motor deceleration
Determines the relationship between fixed boost
and terminal volts. There are two settings:
FALSE produces the terminal volts profile shown
below (with Auto Boost set to 0.0 %). In this mode
AUTO BOOST (CL08) should also be set to
provide optimum low speed performance.
TRUE emulates the terminal volts profile provided
by the Parker SSD Drives' 601 product. This allows
drop in replacement of the 601 by the 650G.
AUTO BOOST (CL08) has no effect in this
mode.
Simple Mode (CL07 = 1)
100%
Motor
Terminal
Volts
FIXED
BOOST %
Output Frequency
Advanced Mode (CL07 = 0)
This parameter allows for load dependent, stator
resistance voltage-drop compensation. This
correctly fluxes the motor (under load conditions)
at low output frequencies, thereby increasing
available motor torque.. AUTO BOOST is only
used when BOOST MODE is set to 0.
The value of the AUTO BOOST parameter
determines the level of additional volts supplied to
the motor for 100% load.
Setting the value of AUTO BOOST too high can
cause the drive to enter current limit. If this occurs,
the time taken for the drive to reach operating
speed will be extended. Reducing the value of
AUTO BOOST will eliminate this problem.
When set TRUE, the demanded volts are reduced
to minimise energy consumption if the drive is
operating in a steady state at light load.
This parameter contains the motor nameplate full-
load line current
www.comoso.com
Range
0=FALSE
1=TRUE
S
CL14
0=FALSE
1=TRUE
0=NONE
1=FIXED
2=AUTOMATIC
0=FALSE
1=TRUE
BASE
FREQUENCY
0.00 to 25.00 %
0=FALSE
1=TRUE
0.01 to 999.99A
Default
0
1
0
1
0.00 %
0
product
code
dependent
650G AC Drive