Set-Up Using The Sensorless Vector Fluxing Mode; The Autotune Feature - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

4-4
Operating the Drive

Set-up using the Sensorless Vector Fluxing Mode

The drive must be tuned to the motor in use by matching the motor parameters in the drive to
those of the motor being controlled.
IMPORTANT: You MUST use the Autotune feature.
Enter values for the following parameters.

The Autotune Feature

IMPORTANT: You MUST carry out an Autotune if you intend to use the drive in Sensorless Vector
Fluxing Mode. If you are using it in Volts/Hz control an Autotune is not necessary.
The Autotune feature identifies motor characteristics to allow the drive to control the motor.
It loads the values into the parameters below.
Display
Parameter
MAX SPEED
MIN SPEED
ACCEL TIME
DECEL TIME
MOTOR CURRENT
BASE FREQUENCY
JOG SETPOINT
RUN STOP MODE
HEAVY/NORMAL
DUTY
CONTROL MODE
NAMEPLATE RPM
MOTOR POLES
MOTOR VOLTAGE
AUTOTUNE MODE
AUTOTUNE
ENABLE
Display
Description
MAG CURRENT
STATOR RES
LEAKAGE INDUC
MUTUAL INDUC
ROTOR TIME
CONST
www.comoso.com
Default
Brief Description
Default is
Set the speed in Hz at which the 650G
Product Code
will run when the maximum setpoint is
dependent
applied
0.0%
Minimum speed clamp
10.0 s
The time taken for the 650G output
frequency to ramp up from zero to MAX
SPEED
10.0 s
The time taken for the 650G output
frequency to ramp down from MAX
SPEED to zero
Default is
Enter the motor nameplate full-load line
Product Code
current
dependent
Default is
Enter the output frequency from the motor
Product Code
nameplate
dependent
10.0 %
Drive speed setpoint whilst jogging
0
Selects a type of "ramp to standstill", for
when RUN signal is removed
0
Selects between Heavy or Normal mode
of operation
SENSORLESS
This parameter contains the main method
VEC (1)
of motor control used by the drive, and
by default is set to VOLTS/HZ
1445.0
Enter the motor nameplate full-load rated
speed. This is the motor speed in rpm at
base frequency minus full load slip
4-pole
Enter the number of motor poles shown
on the motor nameplate
Default is
Enter the motor nameplate voltage at
Product Code
base frequency
dependent
0
Selects the Autotune operating mode.
0
Enables the Autotune feature
Note
Magnetising current. Not measured by
Stationary Autotune
Per phase stator resistance
Per phase stator leakage inductance
Per phase mutual inductance
Rotor time constant. This is identified from
magnetising current and motor nameplate rpm
650G AC Drive