Drive Power
(kW/hp)
0.25/0.3
0.37/0.5
0.55/0.75
0.75/1.0
Drive Power
(kW/hp)
1.1/1.5
1.5/2.0
Drive Power
(kW/hp)
0.37/0.5
0.55/0.75
0.75/1.0
1.1/1.5
1.5/2.0
2.2/3.0
650S AC Drive

Electrical Ratings

Motor power, output current and input current must not be exceeded under steady state operating
conditions.
Maximum Motor dv/dt = 10,000V/μs. This can be reduced by adding a motor choke in series with
the motor. Contact Parker SSD Drives for recommended choke details.
Local wiring regulations always take precedence. Select cable rated for the drive.
The supply must be protected with a fuse (or Type B RCD) rated to the supply cable.
FRAME 1 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Surge Current
(A)
peak/rms for 10ms (A)
19/12
4.2
19/12
6.2
20/14
7.9
22/15
10.5
FRAME 2 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Surge Current
(A)
peak/rms for 10ms (A)
24/17
13.8
25/18
16.0
FRAME 2 : 3-Phase (IT/TN), 400V
Input Current @ 10kA
(A)
2.5
3.3
4.1
5.9
7.5
9.4
Output Current @ 40
o
C
(A) ac
1.5
2.2
3.0
4.0
o
Output Current @ 40
C
(A) ac
5.5
7.0
Output Current @ 40
o
C
(A) ac
1.5
2.0
2.5
3.5
4.5
5.5
Technical Specifications
Maximum Power Loss
(W)
26
32
41
52
Maximum Power Loss
(W)
65
82
Maximum Power Loss
(W)
26
32
40
55
61
70
9-5