Electrical Ratings (400V Build Variant - Parker AC30V series Manual

Variable speed drive
Hide thumbs Also See for AC30V series:
Table of Contents

Advertisement

F-4
Technical Specifications

ELECTRICAL RATINGS (400V BUILD VARIANT)

Product Code
FRAME D :
Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit
current 5kA.
Normal Duty (Output Overload Motoring 110% for 60s)
31V-4D0004...
31V-4D0005...
31V-4D0006...
31V-4D0008...
31V-4D0010...
31V-4D0012...
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 0.5s short term rating)
31V-4D0004...
31V-4D0005...
31V-4D0006...
31V-4D0008...
31V-4D0010...
31V-4D0012...
Power Supply = 380-480V ±10%, 50/60Hz ±5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Motor Power Output Current
(A)
1.1kW
3.5
1.5Hp
3.0
1.5kW
4.5
2Hp
3.4
2.2kW
5.5
3Hp
4.8
3kW
7.5
4kW
10.0
5Hp
7.6
5.5kW
12.0
7.5Hp
11
0.75kW
2.5
1Hp
2.1
1.1kW
3.5
1.5Hp
3.0
1.5kW
4.5
2Hp
3.4
2.2kW
5.5
3Hp
4.8
3kW
7.5
4kW
10.0
5Hp
7.6
Input Current
Estimated
Switching Frequency (kHz)
(A)
Efficiency
nominal / maximum
4
95%
3.5
5.3
96%
4.5
7.6
97%
6.4
6.5
97%
8.0
97%
6.6
10.6
97%
9.4
2.9
95%
2.4
4.0
95%
3.5
5.3
96%
4.5
5.2
97%
4.6
6.5
97%
8.0
97%
6.6
Output Current
Derate %/kHz
4 / 16
2.4%
4 / 16
3.7%
4 / 16
4.5%
4 / 16
4.0%
4 / 16
3.9%
4 / 16
3.5%
4 / 16
1.0%
4 / 16
3.1%
4 / 16
4.3%
4 / 16
3.8%
4 / 16
3.8%
4 / 16
3.3%