Certification for the Drive
0A = 0 Volts Analogue
0D = 0 Volts Digital
PE = Protective Earth
f = External Filter
VSD = Variable Speed Drive
PLC = Programmable Logic Controller

Sensitive Equipment

The proximity of the source and victim circuit has a large effect on radiated coupling. The
electromagnetic fields produced by VSDs fall off rapidly with distance from the cabling/cubicle.
Remember that the radiated fields from EMC compliant drive systems are measured at least 10m
from the equipment, over the band 30-1000MHz. Any equipment placed closer than this will see
larger magnitude fields, especially when very close to the drive.
Do not place magnetic/electric field sensitive equipment within 0.25 metres of the following
parts of the VSD system:
Variable Speed Drive (VSD)
EMC output filters
Input or output chokes/transformers
The cable between VSD and motor (even when screened/armoured)
Connections to external braking chopper and resistor (even when screened/armoured)
AC/DC brushed motors (due to commutation)
DC link connections (even when screened/armoured)
Relays and contactors (even when suppressed)
From experience, the following equipment is particularly sensitive and requires careful
installation.
Any transducers which produce low level analog outputs (<1V) , e.g. load cells, strain
gauges, thermocouples, piezoelectric transducers, anemometers, LVDTs
Wide band width control inputs (>100Hz)
AM radios (long and medium wave only)
Video cameras and closed circuit TV
Office personal computers
Capacitive devices such as proximity sensors and level transducers
Mains borne communication systems
Equipment not suitable for operation in the intended EMC environment, i.e. with
insufficient immunity to new EMC standards
to motor
to motor
screened
VSD
VSD
f
f
PE
PE
PE
0A
0D
PE
0A
0D
Analogue Clean Earth
Dirty Earth
STAR POINT
110V
Control
Figure 10-2 Star Point Earthing
www.comoso.com
U-clip used to terminate screen
to motor
connection to the back panel
screened
VSD
f
f
PE
0A
0D
PE
PE
Digital Clean Earth
Incoming Safety Earth (PE)
Back Panel
PLC
Metal Work Earth
0D
Doors
Back
Metal
Panel
Work
24V Control
unscreened signals
Signal/Control Screen
all screened signals not
going directly to a VSD
650G AC Drive