Control Terminal Description Frames C, D, E & F; Motor Thermistor Connections - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

Terminal
Description
(SELV)
Scn
RS485 option Scn=Screen (shield)
B
RS485 option B=RxB/TxB
A
RS485 option A=RxA/TxA
P3
P3
RL1A
User Relay
RL1B
User Relay
13
DIN7 (ENC B) Configurable digital input
12
DIN6 (ENC A) Configurable digital input
11
DIN5
10
DIN4/
DOUT2
9
DIN3/
DOUT1
8
DIN2
7
DIN1
6
+24V
5
AOUT1
4
10VREF
3
AIN2
2
AIN1
1
0V
* The total current available is 150mA, either individually or as the sum of terminal 6 & 10.

Motor Thermistor Connections

This input is provided to detect over-temperature in motors fitted with an internal thermistor.
There is no polarity to the thermistor connections.
IMPORTANT: This input provides "Basic" insulation only to the SELV control circuits and assumes the
motor has "Basic" insulation to the windings/mains circuits.
The thermistor type supported is PTC `Type A' as defined in IEC 34-11 Part 2. The drive uses
the following resistance thresholds:
If the motor is not fitted with an internal
thermistor, you should disable the thermistor
trip function either by setting INVERT
THERMISTOR INPUT (
linking the thermistor terminals.
650G AC Drive
Control Terminal Description Frames C, D, E & F
Application 1 Default Function
(for other Applications refer to Chapter 13: "Applications")
RS232 port for use with remote-mounted 6521 and 6901
Keypad or programming PC
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
Not Coast Stop - configurable digital input:
0V = drive may run, 24V = Coast to Stop
Configurable digital input/output
Not Stop (input):
24V = RUN FWD & RUN REV signals latched
0V = RUN FWD & RUN REV signals not latched
Configurable digital input/output
Jog (input):
0V = Stop, 24V = Jog
Direction – configurable digital input:
0V = Remote Forward, 24V = Remote Reverse
Run Forward – configurable digital input: 0V = Stop, 24V =
Run
24V supply for digital I/O
Ramp Output – configurable analog output (10mA maximum
loading)
10V reference (10mA maximum loading)
Speed Trim – analog input 2
Speed Setpoint – analog input 1. If unused, tie this input to
0V.
0V reference for analog/digital I/O
Rising temperature trip resistance:
Falling temperature trip reset resistance:
S
Ot) to 1, or by
www.comoso.com
Installing the Drive
0-250Vac/24Vdc 6A
0-250Vac/24Vdc 6A
0-24V source open
1650 to 4000
750 to 1650
TRIPS MENU
3-14
Range
-
-
-
-
0-24V
0-24V
0-24V
collector *
0-24V
0-24V
0-24V
*
0-10V
10V
0-10V, 0-5V
0-20mA, 4-20mA
0-10V, 0-5V
0V

Advertisement

Table of Contents
loading

Table of Contents