Electrical Ratings (Master + 1 Slave) - Parker 690+ Series Product Manual

Hide thumbs Also See for 690+ Series:
Table of Contents

Advertisement

Electrical Ratings (Master + 1 Slave)

Motor power, output current and input current must not be exceeded under steady state operating conditions.
For all units:
Maximum Switching Frequency : 2kHz (Note 9), Input Bridge I
2 drive 690K : 6 & 12 Pulse Compatible
NOTES:
1.
IMPORTANT : 3% line impedance MUST be provided for each unit, and is assumed in the quoted input
current values. Failure to do so will severely shorten DC link capacitor lifetime and could result in damage to the
bridge. Refer to AC Line Choke table.
2.
Input currents for kW ratings are at 400V 50Hz ac input, and for Hp ratings at 460V 60Hz ac input.
3.
Short circuit protection Semiconductor Fuses should be installed in the 3-phase supply to each drive module in
the Frame K to protect the input bridge. Circuit breakers or HRC fuses will not protect the input bridge.
4.
Fundamental Input Power Factor : 0.95
5.
Output Voltage (maximum) = Input Voltage
6.
Output Frequency : 0 to 120Hz
7.
Fan Inlet Temperature Range : 0 to 40°C
8.
Earth Leakage Current : >>100mA. Product must be permanently earthed.
9.
True value given, note that the MMI will display 3kHz
380-460V ±10%, 45-65Hz
Suitable for earth referenced (TN) and non earth referenced (IT) supplies.
Motor Power
Model Number
@ 400V
(Europe)
(kW)
Motor Power
Catalog Number
@ 460V
(North America)
(Hp)
2x 690PG-X/1800
355 kW
2x 690+G-X/0300
600 Hp
2x 690PH-X/2200
400 kW
2x 690+H-X/0350
700 Hp
2x 690PH-X/2800
500 kW
2x 690+H-X/0450
800 Hp
2x 690PJ-X/3150
600 kW
2x 690+J-X/0500
1000 Hp
2x 690PG-X/1800
400 kW
2x 690+G-X/0300
700 Hp
2x 690PH-X/2200
475 kW
2x 690+H-X/0350
800 Hp
2x 690PH-X/2800
600 kW
2x 690+H-X/0450
1000 Hp
2x 690PJ-X/3150
650 kW
2x 690+J-X/0500
1100 Hp
690+ Series AC Drive
1 SLAVE
Input Current Per Drive
@ 400V 50Hz
(A)
Output
Current
Input Current Per Drive
(A)
@ 460V 60Hz
(A)
Notes 1 & 2
CONSTANT TORQUE (Output Overload Motoring 150% for 60s)
331
685
358
364
798
409
461
988
470
549
1120
584
QUADRATIC TORQUE (Output Overload Motoring 110% for 60s)
365
798
411
428
912
461
544
1120
581
588
1235
636
www.comoso.com
Technical Specifications
2
t : 813000A
1 MASTER
Total Input Current
@ 400V 50Hz
(A)
Total Input Current
@ 460V 60Hz
(A)
Notes 1 & 2
663
716
727
818
921
940
1097
1168
731
822
855
922
1088
1162
1175
1272
8-7
2
s,
Input
Total
Fuse
Total
Heatsink
Rating
Power
Power
(A)
Loss
Loss
(kW)
(kW)
Note 3
400
6.0
6.8
450
7.0
8.0
550
9.1
9.9
600
11.0
11.9
450
7.3
8.0
500
8.5
9.2
600
10.4
11.4
650
12.3
13.2

Advertisement