Electrical Ratings - Parker 650G Frame 1 Product Manual

Table of Contents

Advertisement

9-4
Technical Specifications

Electrical Ratings

Drive
Power
(kW/hp)
peak/rms for 10ms (A)
0.25/0.3
0.37/0.5
0.55/0.75
0.75/1.0
Drive
Power
(kW/hp)
peak/rms for 10ms (A)
1.1/1.5
1.5/2.0
Drive
Power
(kW/hp)
0.37/0.5
0.55/0.75
0.75/1.0
1.1/1.5
1.5/2.0
2.2/3.0
Drive
Power
(kW/hp)
2.2/3.0
Drive
Power
(kW/hp)
2.2/3.0
3.0/4.0
4.0/5.0
Drive
Power
(kW/hp)
3.0/4.0
4.0/5.0
5.5/7.5
7.5/10.0
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Maximum Motor dv/dt = 10,000V/µs. This can be reduced by adding a motor choke in series
with the motor. Contact Parker for recommended choke details.
Local wiring regulations always take precedence. Select cable rated for the drive.
The supply must be protected with a fuse (or Type B RCD) rated to the supply cable.
FRAME 1 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Surge Current
19/12
19/12
20/14
22/15
FRAME 2 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Surge Current
24/17
25/18
FRAME 2 : 3-Phase (IT/TN), 400V
Input Current @ 10kA
(A)
2.5
3.3
4.1
5.9
7.5
9.4
FRAME 3 : 1-Phase (IT/TN), 230V
Input Current @ 7.5kA
(A)
22.0
FRAME 3 : 3-Phase (IT/TN), 230V
Input Current @ 7.5kA
(A)
14.3
18.1
23.1
FRAME 3 : 3-Phase (IT/TN), 400V
Input Current @ 10kA
(A)
11.1
13.9
18.0
23.6
Output Current @ 40
(A) ac
(A)
4.2
1.5
6.2
2.2
7.9
3.0
10.5
4.0
Output Current @ 40
(A) ac
(A)
13.8
5.5
16.0
7.0
Output Current @ 40
(A) ac
1.5
2.0
2.5
3.5
4.5
5.5
Output Current @ 40
(A) ac
9.6
Output Current @ 40
(A) ac
9.6
12.3
16.4
Output Current @ 40
(A) ac
6.8
9.0
12.0
16.0
o
C
Maximum Power
Loss
(W)
26
32
41
52
o
C
Maximum Power
Loss
(W)
65
82
o
C
Maximum Power
Loss
(W)
26
32
40
55
61
70
o
C
Maximum Power
Loss
(W)
112
o
C
Maximum Power
Loss
(W)
103
133
180
o
C
Maximum Power
Loss
(W)
80
100
136
180
650G AC Drive

Advertisement

Table of Contents
loading

This manual is also suitable for:

650g frame 2650g frame 3650g