Trips and Fault Finding
ID
Trip Name
12
DISPLAY/KEYPAD
13
LOST COMMS
14
CONTACTOR FBK
15
SPEED FEEDBACK
16
AMBIENT TEMP
17
MOTOR
OVERTEMP
18
CURRENT LIMIT
21
LOW SPEED OVER I
22
10V FAULT
25
DC LINK RIPPLE
27
OVERSPEED
28
ANOUT FAULT
29
DIGIO 1 (T9)
FAULT
www.comoso.com
Possible Reason for Trip
Keypad has been disconnected from drive whilst drive is
running in Local Control:
Keypad accidentally disconnected from drive (indicated
over Comms, or by second keypad)
Lost communications:
COMMS TIMEOUT parameter set too short
Master device failed
Wiring broken
Incorrect Comms setup
Contactor feedback signal lost:
Check connection to the terminal wired to "contactor
closed" parameter in Sequencing Logic (non-standard
configuration)
Speed feedback:
SPEED ERROR > 50.00% for 10 seconds
Ambient temperature:
The ambient temperature in the drive is too high
The motor temperature is too high:
Excessive load
Motor voltage rating incorrect
FIXED BOOST level set too high
Prolonged operation of the motor at low speed without
forced cooling
Break in motor thermistor connection
Software overcurrent trip:
If the current exceeds 180% of stack rated current for a
period of 1 second, the drive will trip. This is caused by
shock loads. Remove the shock load.
ACCEL TIME and/or FIXED BOOSTset too high
DECEL TIME set too low
The motor is drawing too much current (>100%) at zero
output frequency:
FIXED BOOST level set too high
10V fault:
+10V REF overload warning (terminal 4) -
10mA maximum
The dc link ripple voltage is too high:
Check for a missing input phase
Overspeed:
>150% base speed when in Sensorless Vector mode
AOUT overload on terminal 5:
10mA maximum
DIN3 overload on terminal 9:
20mA maximum
650G AC Drive