Installing the Drive
RS485/RS232 Communication Module (Frames 1, 2 & 3)
You can create a network of drives by linking a Master (PC/PLC) to one or more 650G drives
fitted with this module.
Plug this Communication Module on to the front of the 650G drive, replacing the keypad.
It converts signals from the host 650G drive into RS485 or RS232, and vice versa, so that
information can be shared between the Master and 650G drive(s).
Wiring is very simple - all connections are SELV (Safe Extra Low Voltage). Select to use
RS485 or RS232 by wiring to the appropriate terminal on the module.
Note: RS485 and RS232 terminals cannot be used simultaneously.
We recommend you ground the module to the system earth using the Functional Earth terminal.
9-Way / 25-Way
650 Drive
PC/PLC
with
Module
D-Type
Connector
Scn
B
B
A
A
To PC/PLC
Chassis
Drive
Wiring Specifications
Network Type
Connections
Signal Levels
Receiver Input
Impedance
Maximum Cable Length
Maximum Baud Rate
Maximum Number of
Units
www.comoso.com
PC/PLC
Drive
Drive
Master
master to single/multiple slave
RS485 Connections
RS485 Connections
2-Wire Shielded Twisted-Pair
A=RxA/TxA, B=RxB/TxB, Shield
To RS485 Standard
¼ Unit Load
1200m (4000ft)
57.6kbaud
32 including slaves and masters
PC/PLC
9-Way or 25-Way
D-Type Connector
0V
Tx
Rx
Functional
Earth
PC/PLC
Drive
Master
master to single slave only
RS232 Connections
RS232 Connections
3-Wire Un-Shielded Cable
Rx, Tx, Ground (0V)
To RS232 Standard
3 k minimum
7k maximum
3 metres
57.6kbaud
2: 1 master and 1 slave
only
650G AC Drive