650G Frames C, D, E & F
H
Figure 1 Mechanical Dimensions for 650G Drives
Frame C
Frame D
Frame E
Frame F
For details of a through-panel mounting option for Frames D & E refer to pages 3-6 and 3-8
respectively.

Mounting the Drive

To DIN mount the unit, hang the unit on the top DIN rail and push the unit onto the bottom DIN
rail until it snaps in to position. Secure with a lower screw fixing. To release the unit, use a flat
bladed screwdriver as shown.

Ventilation

The drive gives off heat in normal operation and must therefore be mounted to allow the free
flow of air through the ventilation slots and heatsink. Maintain minimum clearances for
ventilation as given in the tables below to ensure adequate cooling of the drive, and that heat
generated by other adjacent equipment is not transmitted to the drive. Be aware that other
equipment may have its own clearance requirements. When mounting two or more 650G units
together, these clearances are additive. Ensure that the mounting surface is normally cool.
650G AC Drive
Top Cover increased height shown by H2
W
H1
W 1
Approximate Frame C shown for illustration purposes
Models
Max. Weight
H
kg/lbs
9.3/20.5
348.0
(13.70)
17.4/38.2
453.0
(17.8)
32.5/72
668.6
(26.3)
41/90.4
720.0
(28.3)
All dimensions are in millimetres (inches)
www.comoso.com
Installing the Drive
D
Heat
Control
Sink
H1
H2
W
335.0
365.0
201.0
(13.19)
(14.37)
(7.91)
440.0
471.0
252.0
(17.3)
(18.5)
(9.92)
630.0
676.0
257.0
(24.8)
(26.6)
(10.1)
700.0
Not
257.0
(27.6)
applicable
(10.1)
3-2
H2
W1
D
Fixings
150
208.0
Slot 7mm wide
(5.90)
(8.19)
Use M5 or M6
fixings.
150
245.0
Slot 7mm wide
(5.90)
(9.65)
Use M5 or M6
fixings.
150.0
312
Use M6 fixings
(5.9)
(12.3)
150.0
355.0
Use M6 fixings
(5.9)
(14.0)